Common wires and selective wires
A Lee-Dan system uses two kinds of wire.
- Common wires run to every apartment. They carry the things everyone shares: the voice in each direction and the door release.
- A selective wire runs to one apartment only. It carries that apartment's call signal from its button at the door.
So each apartment station has several common wires plus one selective wire of its own.
| System | Station | Common wires | Selective wire | Total at each station |
|---|---|---|---|---|
| Three-wire | IR-203 | 2 | 1 | 3 |
| Four-wire | IR-204 | 3 | 1 | 4 |
| Five-wire | IR-205 | 4 | 1 | 5 |
The cable running up the building carries the common wires plus one selective wire for every apartment on that line. A ten-apartment riser on a four-wire system needs at least thirteen conductors: three common and ten selective.
Why the difference shows up as faults
- A fault on a selective wire affects one apartment. That apartment's buzzer stops and everyone else is fine.
- A fault on a common wire affects everyone on that line. A whole column of apartments loses voice or door release together.
- Two selective wires touching makes two apartments ring together.
This is why the first question we ask is how many apartments are affected. The answer usually tells us which kind of wire has failed before we arrive.
Why the wire count matters when replacing a station
The three station models look alike and are built for different wire counts. A four-wire station on a three-wire line has a terminal with nothing to connect to, and it will not work. Putting a wire on the wrong terminal can short a common wire and take out the whole line.
If building staff are replacing a station, photograph the wires on their terminals before you remove anything, and fit the same model that came off.
Why it matters for upgrades
Wire that is already in the walls is the most valuable part of an old system. Newer two-wire video intercoms, such as the DT-607 panels and DX-471 monitors, run on two wires. A building wired for a three, four or five-wire Lee-Dan often has enough good conductors to carry one, which means video without opening walls. We test the existing wire before quoting. See replacement and upgrades.
Diagrams
Swipe sideways to see the whole diagram.
Common questions
How do I know if my building is three, four or five-wire?
Count the wires connected to the back of an apartment station, or read the model number on it: IR-203 is three, IR-204 is four, IR-205 is five.
Is intercom wiring dangerous to touch?
The wiring to the stations is low voltage. The transformer that feeds the amplifier is connected to mains power and should be left to an electrician or intercom technician.
Can old intercom wire be reused for a new system?
Often. It depends on how many conductors there are and their condition, which we test on site.